How to Determine Values of Transformer Bushing

Determining a transformer bushing typically involves selecting or designing a bushing that meets the electrical, mechanical, and thermal requirements of the transformer. It’s not about a single formula, but rather a design process based on key parameters. Below is a structured breakdown:


1. Electrical Rating Calculation

This defines the voltage insulation level and current carrying capacity of the bushing.

a. Voltage Rating

  • Must match or exceed the transformer’s system voltage and Basic Insulation Level (BIL).
  • BIL is chosen based on IEC/IEEE standards for system voltage.
System Voltage (kV)Typical BIL (kV)
66325
132550
2201050
4001425

b. Current Rating

  • Based on load current of transformer winding.
  • Bushing conductor must have sufficient cross-section for thermal limits (e.g., 1200 A, 2000 A, etc.).

Use:
I = S / (√3 × V)
Where:

  • I = current (A)
  • S = apparent power (VA)
  • V = line voltage (V)

2. Thermal Considerations

  • Bushing must dissipate heat generated by load current.
  • Important for high-current bushings.
  • Use manufacturer’s thermal curve or simulation to ensure temperature rise stays within limits.

3. Creepage Distance Calculation (for outdoor bushings)

  • Determines length of the insulating surface to avoid flashover.

Required Creepage Distance (mm) =
Pollution Severity Factor × System Voltage (kV)

Pollution LevelCreepage Factor (mm/kV)
Light16
Medium20
Heavy25
Very Heavy31

Example:
For a 220 kV system in a heavily polluted area:
Creepage distance = 220 × 25 = 5500 mm


4. Mechanical Strength

Ensure mechanical strength is adequate to withstand:

  • Short-circuit forces
  • Terminal weight and wind loading (especially for outdoor bushings)

5. Type of Bushing (Based on Insulation Type)

Choose based on application, environment, and voltage:

  • OIP (Oil-Impregnated Paper)
  • RIP (Resin-Impregnated Paper)
  • Porcelain or Polymer Composite housing
  • Dry-type for indoor use

6. Mounting Dimensions

  • Based on transformer tank design.
  • Must match standardized flange sizes (e.g., per IEC 60137 or ANSI standards).
  • Determine oil-side and air-side lengths, depending on transformer height and clearances.

Summary Checklist for Bushing Calculation

ParameterConsideration
Voltage Rating≥ Transformer system voltage and BIL
Current Rating≥ Transformer full-load current
Creepage DistanceBased on pollution class
Insulation TypeOIP, RIP, RBP, etc.
Thermal DesignAcceptable temperature rise
Mechanical RequirementsShort-circuit and wind force withstand
Mounting & DimensionsFlange size, air/oil side length